CIMPLICITY REST API Web Service
CIMPLICITY REST API Web Service / All Operations Resource Group / /projects/{projectId}/points (Post)
In This Topic
    Post/projects/{projectId}/points
    In This Topic
    Description
    Creates or updates an array of points in the project
    Parameters
    NameDescriptionData Type
    the id of the projectstring
    Request (application/json)

    The request body is of type object.

    Overview

    Points : Array[CimPoint]
    AttributeSet : string
    string indicating the Attribute set to be used for the point. Defaults to the empty string when creating a new point.
    DataLen : integer
    is a read-only integer that contains the length of the data. The value is configured by setting the Point Type ID
    DeadBand : string
    is a variant with a string representation of 10 characters or less. Larger values will be rejected. Enter a value defining the tolerance for alarm conditions in this field. The deadband cushions the generation of alarms when a point value fluctuates at an alarm limit. Defaults to the empty string for new points. To remove the deadband set it to an empty string (e.g. "".)
    DerivedPoint : CimDerivedPoint
    Contains the properties pertaining to Derived Point Configuration
    CalculationType : CimPointCalcTypesEnum
    Specifies calculation types of points
    InitState : CimDpInitStateEnum
    Specifies initial value for a global or derived point.
    InitValue : string
    is string containing the initial value for the point.
    Local : boolean
    is boolean indicating if the point is local. Local points can be used to hold intermediate values of expressions. The value of local points are not available to applications, they are only used internally by the derived point process to perform calculations.
    PointExpression : string
    is string containing the expression for the point.
    PointSetInterval : string
    is string containing the interval to update the timer counter point. The format is HH:MM:SS using a 24 hour clock.
    PointSetTime : string
    is string containing the start time for the timer counter point. The format is HH:MM:SS using a 24 hour clock
    ProcessID : string
    is a string specifying the derived point process supporting this point. Normally this will be 'SPM' or '_PTDP_RP'. This must identify a valid derived point processor process ID. It should not be changed unless you are using structure point processing
    ResetPointID : string
    is a string containing the name of the reset point.
    RolloverVal : integer
    is a long integer defining the roll over value for delta accumulator function.
    VarianceValue : integer
    is long integer defining the maximum variance value to be used for delta accumulator functions.
    Description : string
    is a mixed case string of 40 characters or less. Longer strings will be automatically truncated. Descriptions also appear as the tool-tip for the point when browsing or configuring points. Defaults to the empty string when creating a new point.
    DevicePoint : CimDevicePoint
    object contains the device information for a CIMPLICITY point.
    Address : string
    is a string indicating the device specific address of the point
    AddressOffset : integer
    is an integer indicating the address offset of the point. Typically used for addressing a boolean point in an analog domain
    AddressType : CimMMSAddressTypeEnum
    MMS types
    AnalogDeadband : string
    is an variant containing the analog deadband for the point. The point will not be updated until a change that exceeds the deadband is read.
    DelayLoad : boolean
    is boolean indicating the point should only be loaded into memory if it's requested by an application. Defaults to False.
    DeviceID : string
    is a string indicating the device the point is on
    JustInTime : boolean
    is a boolean used to enable or disable Just-In-Time. Note this is only available when this is a class Data Item comming from the Class configuration
    PollAfterSetpoint : boolean
    is boolean indicating if the point should be polled immediately after a setpoint. If False, the point is not polled until the next scheduled scan cycle
    ScanRate : integer
    is an integer indicating the scan rate of the point in multiples of the base scan rate of the communications port.
    TriggerType : CimDeviceTriggerEnum
    defines the trigger condition for a device point. See the Point Configuration documentation for additional information
    TriggerValue : string
    is variant containing the trigger value. Trigger value is used when specifying a CimDevicePoint.TriggerType relation that requires a value
    UpdateCriteria : CimUpdateCriteriaEnum
    defines update criterias available for device points. The particular types of update that are actually available depend on the device communication module being used
    DisplayFormat : string
    is a string used to specify the display format for the point. DisplayFormat uses the "C" language format specifiers
    DisplayLimitHigh : string
    is a variant with a string representation of 10 characters or less. Larger values will be rejected. Display limits can be used as the animation limits when graphically displaying a point. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    DisplayLimitLow : string
    is a variant with a string representation of 10 characters or less. Larger values will be rejected. Display limits can be used as the animation limits when graphically displaying a point. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    Elements : integer
    is an integer containing the number of elements in the point. Defaults to 1 for new points
    EngineeringUnits : CimEngineeringUnits
    object contains the conversion information for converting a point from raw device units to real-world units. Conversion can either be linear or based on a conversion expression
    EuExpression : string
    is a string containing the equation used to convert the value from device units to engineering units. To use a custom expression you must first disable the linear conversion for the object. If the point is not read-only a reverse expression must be specified to allow a setpoint in engineering units to be translated back to device units. It is your responsibility to make sure these expressions yield the correct results
    EuLabel : string
    is a string containing the EuLabel. Note you cannot specify an EuLabel if using a measurement unit for the point
    EuRevExp : string
    is a string containing the equation used to convert the value from engineering units to device units. To use a custom expression you must first disable the linear conversion for the object. A forward expression must also be specified. It is your responsibility to make sure these expressions yield the correct results
    HighConvValue : string
    is a variant containing the high converted value used for linear conversion with a string representation of 10 characters or less. Larger values will be rejected. To use linear conversion you must set linear conversion to True
    HighRawValue : string
    is a variant containing the upper raw value used for linear conversion with a string representation of 10 characters or less. Larger values will be rejected. To use linear conversion you must set linear conversion to True
    LinearConversion : boolean
    is a boolean indicating if the conversion is linear or custom
    LowConvValue : string
    is a variant containing the low converted value used for linear conversion with a string representation of 10 characters or less. Larger values will be rejected. To use linear conversion you must set linear conversion to True.
    LowRawValue : string
    is a variant containing the low raw value used for linear conversion with a string representation of 10 characters or less. Larger values will be rejected. To use linear conversion you must set linear conversion to True.
    EnterprisePoint : boolean
    is an boolean indicating if the point should be exported to an enterprise server. Defaults to False when creating a new point
    EnumFields : Array[CimPointEnumField]
    As an alternative to the EnumerationID all the fileds used for this point may be provided, and an enumeration for this point will be generated
    Text : string
    The Text property gets and sets the text of the point enum field.
    Value : integer
    The numeric value of the point enum field.
    SetpointAllowed : boolean
    The SetpointAllowed property gets and sets if a setpoint is allowed with this enum text for the point.
    EnumerationID : string
    is a string indicating the Point Enumeration to be used for the point. Defaults to the empty string when creating a new point.
    EuExists : boolean
    is a boolean indicating if the point uses EU Conversion. Setting this to False will remove EU Conversion for the point. Setting this to True will enable EU Conversion for the point. Defaults to False for a new point
    Expressions : Array[CimClassDataItemExpression]
    is a list that contains the expressions for this dataitem
    FirstOperandNum : number
    is number that hlds the first (or left hand) side of the opperand if the value is to be treated as a number. Use CimClassDataItemExpression.FirstOperandString if your value is a string
    FirstOperandString : string
    is string that hlds the first (or left) hand side of the opperand. Use CimClassDataItemExpression.FirstOperandNum if your value is a number
    ID : string
    is a read only attribute that represents the ID of this expression
    Operator : CimExpressionOperandTypesEnum
    Specifies the browser type
    SecondOperandNum : number
    is number that hlds the first (or left) hand side of the opperand if the value is to be treated as a number. Use CimClassDataItemExpression.SecondOperandString if your value is a string
    SecondOperandString : string
    is string that hlds the second (or right hand) side of the opperand. Use CimClassDataItemExpression.SecondOperandNum if your value is a number
    Extra : integer
    is an integer representing the extra data for the point. Defaults to 0 when creating a new point
    InvertAvailabilityTrigger : boolean
    is a boolean used to enable or disable availability trigger value inversion for a point. Defaults to FALSE for a new point
    Level : integer
    is an integer representing the level for the point. Defaults to 0 when creating a new point
    LogData : boolean
    is a boolean value indicating whether the point is logged through the database logger default logging option (DATA_LOG). To log the point to a table other than the default, use the CimTable methods. Defaults to the false when creating a new point
    LogDataHistorian : boolean
    is a boolean value indicating whether the point is logged through Historian. Note The Historian OPC Interface option must be selected in the project properties. and the Historian client must be installed and configured. Defaults to the false when creating a new point
    MeasurementUnitID : string
    is a string indicating the Measurement Unit ID to be used for conversion of the point. Defaults to the empty string when creating a new point
    MeasurementUnit : CimMeasurementUnit
    Represents measurement unit.
    UnitId : string
    The string identifier of the measurement unit.
    Description : string
    Contains informative information about the measurement unit.
    FullName : string
    Contains the full name of the measurement unit such as ”hour” or ”meter per second”.
    DisplayLabel : string
    The display label of the measurement unit is typically the abbreviation of the measurement unit, for example ”h” for hour or ”m/s” for meter per second.
    NamespaceUri : string
    Identifies the organization (company, standards organization) that defines the measurement unit.
    NumericUnitId : integer
    Numeric identifier for programmatic evaluation. -1 is used if a unitId is not available.
    OPCUA_NodeID : string
    is a read-only string containing the OPC UA NodeID for the point
    PointAlarm : CimPointAlarm
    object contains the point alarm information for a CIMPLICITY point
    Alarm : CimAlarm
    object provides an interface to CIMPLICITY Alarm configuration
    AckTimeout : integer
    is a long integer that indicates when automatic alarm acknowledgement should happen. Valid values are -1 - Immediate Acknowledgement 0 - No Automatic Acknowledgement (default) >0 - Number of minutes to wait before automatically acknowledging alarm
    AlarmClass : string
    is a string containing the class of the alarm
    AlarmDescription : string
    is a string containing the description of the alarm, This attribute shall be ignored in case of point alarm
    AlarmID : string
    is a string containing the Alarm ID. When accessed from a Point Alarm, this property is read-only because the Alarm ID is the same as the Point ID
    AlarmMessage : string
    is a string containing the alarm message. Note When accessed from a Point Alarm, this property is read-only because the structure of the point alarm message defines the alarm message
    AlarmTypeID : string
    is a string containing the alarm type id of the alarm. When accessed from a Point Alarm, this property is read-only because the structure of the point alarm message defines the Alarm Type Id
    Changeapproval : CimChangeapprovalEnum
    defines different change approval data setting. The numeric value of these enumerations can be used in an expression of a class data item for the $APPROVAL_TYPE field
    DeleteOpt : CimAlarmDelOptEnum
    defines the deletion options available for an alarm
    HelpFileName : string
    is a string containing the name of the alarm help file. The string must be prefixed with AM_HELP:\ in order for the file to be found by the alarm viewer and must have the extension HLP.
    HiAckTimeout : integer
    The CimAlarm.HiAckTimeout is a long integer that indicates when automatic alarm acknowledgement should happen while the alarm in the Warning High state. Valid values are -1 - Immediate Acknowledgement 0 - No Automatic Acknowledgement (default) >0 - Number of minutes to wait before automatically acknowledging alarm
    HiDeleteOpt : CimAlarmDelOptEnum
    defines the deletion options available for an alarm
    HiHiAckTimeout : integer
    The CimAlarm.HiHiAckTimeout is a long integer that indicates when automatic alarm acknowledgement should happen while the alarm in the Alarm High state. Valid values are -1 - Immediate Acknowledgement 0 - No Automatic Acknowledgement (default) >0 - Number of minutes to wait before automatically acknowledging alarm
    HiHiDeleteOpt : CimAlarmDelOptEnum
    defines the deletion options available for an alarm
    HiHiLogOpt : string
    The CimAlarm.HiHiLogOpt is a string that indicates what the alarm transitions in the Alarm High state should be logged. Valid characters are A - Log when acknowledged R - Log when reset D - Log when deleted G - Log when generated
    HiHiRepeatTimeout : integer
    is a long integer that indicates when automatic alarm repeat should occur while the alarm is in the Alarm High state. 0 - No Automatic Repeat (default) >0 - Number of minutes to wait before automatically repeating alarm
    HiHiResetAllowed : boolean
    is a boolean that indicates if the alarm can be manually reset when it is in the Alarm High state
    HiHiResetTimeout : integer
    The CimAlarm.HiHiResetTimeout is a long integer that indicates when automatic alarm reset should happen while the alarm in the Alarm High state. Valid values are -1 - Immediate reset 0 - No Automatic reset (default) >0 - Number of minutes to wait before automatically resetting alarm
    HiLogOpt : string
    The CimAlarm.HiLogOpt is a string that indicates what the alarm transitions in the Warning High state should be logged. Valid characters are A - Log when acknowledged R - Log when reset D - Log when deleted G - Log when generated
    HiRepeatTimeout : integer
    is a long integer that indicates when automatic alarm repeat should occur while the alarm is in the Warning High state. 0 - No Automatic Repeat (default) >0 - Number of minutes to wait before automatically repeating alarm
    HiResetAllowed : boolean
    is a boolean that indicates if the alarm can be manually reset when it is in the Warning High state
    HiResetTimeout : integer
    The CimAlarm.HiResetTimeout is a long integer that indicates when automatic alarm reset should happen while the alarm in the Warning High state. Valid values are -1 - Immediate reset 0 - No Automatic reset (default) >0 - Number of minutes to wait before automatically resetting alarm
    LoAckTimeout : integer
    is a long integer that indicates when automatic alarm acknowledgement should happen while the alarm in the Warning Low state. Valid values are -1 - Immediate Acknowledgement 0 - No Automatic Acknowledgement (default) >0 - Number of minutes to wait before automatically acknowledging alarm.
    LoDeleteOpt : CimAlarmDelOptEnum
    defines the deletion options available for an alarm
    LoLoAckTimeout : integer
    is a long integer that indicates when automatic alarm acknowledgement should happen while the alarm in the Alarm Low state. Valid values are -1 - Immediate Acknowledgement 0 - No Automatic Acknowledgement (default) >0 - Number of minutes to wait before automatically acknowledging alarm
    LoLoDeleteOpt : CimAlarmDelOptEnum
    defines the deletion options available for an alarm
    LoLoLogOpt : string
    is a string that indicates what the alarm transitions in the Alarm Low state should be logged. Valid characters are A - Log when acknowledged R - Log when reset D - Log when deleted G - Log when generated
    LoLoRepeatTimeout : integer
    is a long integer that indicates when automatic alarm repeat should occur while the alarm is in the Alarm Low state. 0 - No Automatic Repeat (default) >0 - Number of minutes to wait before automatically repeating alarm
    LoLoResetAllowed : boolean
    is a boolean that indicates if the alarm can be manually reset when it is in the Alarm Low state
    LoLoResetTimeout : integer
    The CimAlarm.LoLoResetTimeout is a long integer that indicates when automatic alarm reset should happen while the alarm in the Alarm Low state. Valid values are -1 - Immediate reset 0 - No Automatic reset (default) >0 - Number of minutes to wait before automatically resetting alarm
    LoLogOpt : string
    The CimAlarm.LoLogOpt is a string that indicates what the alarm transitions in the Warning Low state should be logged. Valid characters are A - Log when acknowledged R - Log when reset D - Log when deleted G - Log when generated
    LoRepeatTimeout : integer
    is a long integer that indicates when automatic alarm repeat should occur while the alarm is in the Warning Low state. 0 - No Automatic Repeat (default) >0 - Number of minutes to wait before automatically repeating alarm
    LoResetAllowed : boolean
    is a boolean that indicates if the alarm can be manually reset when it is in the Warning Low state
    LoResetTimeout : integer
    is a long integer that indicates when automatic alarm reset should happen while the alarm in the Warning Low state. Valid values are -1 - Immediate reset 0 - No Automatic reset (default) >0 - Number of minutes to wait before automatically resetting alarm
    LogOpt : string
    The CimAlarm.LogOpt is a string that indicates when the alarm should be logged. Valid characters are A - Log when acknowledged R - Log when reset D - Log when deleted G - Log when generated
    MaxStacked : integer
    is a long integer that indicates how many alarms to stack. Defaults to zero if not specified. Maximum value is 20
    Published : boolean
    is a boolean used to enable or disable publishing to SOA for an alarm. Defaults to FALSE for a new alarm
    RepeatTimeout : integer
    is a long integer that indicates when automatic alarm repeat should occur 0 - No Automatic Repeat (default) >0 - Number of minutes to wait before automatically repeating alarm
    ResetAllowed : boolean
    is a boolean that indicates if the alarm can be manually reset
    ResetTimeout : integer
    The CimAlarm.ResetTimeout is a long integer that indicates when automatic alarm reset should happen. Valid values are -1 - Immediate reset 0 - No Automatic reset (default) >0 - Number of minutes to wait before automatically resetting alarm
    Routing : Array[string]
    returns an object containing the alarm routing for the alarm
    Severity : integer
    is a short that indicates the alarm severity
    AlarmConfigured : boolean
    is a boolean indicating if alarming is configured for the point
    AlarmCriteria : CimPointAlarmEnum
    defines types of alarming available
    AlarmDelay : boolean
    is a boolean indicating if the alarm generation should be delayed. When alarm delay is enabled specify the TimeInterval and TimeUnit for the delay. AlarmDelay cannot be used with a Rate of Change alarm criteria
    AlarmHigh : string
    contains a variant indicating the alarm high limit for the point
    AlarmLow : string
    contains a variant indicating the alarm low limit for the point
    AlarmMessage : string
    is a string containing the point alarm message to be used when an alarm is generated for the point
    AlarmOffDelay : boolean
    is a boolean indicating if the moving alarm to normal state should be delayed. When alarm off delay is enabled specify the TimeInterval and TimeUnit for the delay. AlarmOffDelay cannot be used with a Rate of Change alarm criteria
    AlarmStrID : integer
    is a integer containing the Alarm String to use when generating point alarms. Defaults to 1
    AlarmValueUpdate : boolean
    is a boolean indicating if the %VAL field in the alarm message should be updated while the point is in ana alarm state
    DeviationPtID : string
    is a string containing the name of the deviation point. The deviation point must be specified when the alarm criteria is cimAlarmDeviation
    HiDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes into the Warning High state
    HiDelayUnit : CimTimeUnitEnum
    defines units for time values
    HiHiDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes into the Alarm High state
    HiHiDelayUnit : CimTimeUnitEnum
    defines units for time values
    HiHiOffDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes from the Alarm High state to Normal state
    HiHiOffDelayUnit : CimTimeUnitEnum
    defines units for time values
    HiOffDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes from the Warning High state to Normal state
    HiOffDelayUnit : CimTimeUnitEnum
    defines units for time values
    LoDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes into the Warning Low state
    LoDelayUnit : CimTimeUnitEnum
    defines units for time values
    LoLoDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes into the Alarm Low state
    LoLoDelayUnit : CimTimeUnitEnum
    defines units for time values
    LoLoOffDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes from the Alarm Low state to Normal State
    LoLoOffDelayUnit : CimTimeUnitEnum
    defines units for time values
    LoOffDelayInterval : string
    is a variant containing a numeric value indicating the delay interval when alarm goes from the Warning Low state to Normal state
    LoOffDelayUnit : CimTimeUnitEnum
    defines units for time values
    TimeInterval : string
    is a variant containing a numeric value indicating the time interval when using a rate of change or alarm delay
    TimeUnit : CimTimeUnitEnum
    defines units for time values
    WarningHigh : string
    contains a variant indicating the warning high limit for the point
    WarningLow : string
    contains a variant indicating the warning low limit for the point
    PointID : string
    is a string that contains the name of the point. Point ID's are truncated to 256 characters. Since this is the default property of the object, you can omit it when assigning or using it.
    PointState : boolean
    is a boolean used to enable or disable a point. When a point is disabled it is not collected from the device and is unavailable. The point is enabled when its point state is True, disabled when its point state is False. Defaults to True for new points
    PointTypeID : string
    is a string containing the Point Type of the Point. Any of the point types that are available in configuration can be used here such as UINT, USINT, INT, SINT, STRING_20, etc. Must be specified when creating a new point
    Published : boolean
    is a boolean used to enable or disable publishing to SOA for a point. Defaults to FALSE for a new point
    RangeLimitHigh : string
    is a variant with a string representation of 10 characters or less. Larger values will be rejected. Values below the low range limit and above the high range limit will cause the point to be unavailable. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    RangeLimitLow : string
    is a variant with a string representation of 10 characters or less. Larger values will be rejected. Values below the low range limit and above the high range limit will cause the point to be unavailable. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    ReadOnly : boolean
    is an boolean indicating if the point is read-only. Defaults to False for new points
    ResourceID : string
    is a string containing the Factory Resource associated with the point. Must be specified when creating a new point
    SafetyPointID : string
    is an string containing the name of the safety point. The status of a safety point controls whether or not a setpoint is permitted. If the value of the safety point is non-zero and available a setpoint will be permitted. Defaults to the empty string when creating a new point.
    ScreenID : string
    is a string indicating the CimView screen to be associated with the point. Defaults to the empty string when creating a new point
    SetpointLimitHigh : string
    is a variant representing the upper limit for a value when performing a setpoint action with a string representation of 10 characters or less. Larger values will be rejected. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    SetpointLimitLow : string
    is a variant representing the lower limit for a value when performing a setpoint action with a string representation of 10 characters or less. Larger values will be rejected. Defaults to the empty string when creating a new point. To remove a limit set it to an empty string (e.g. "".)
    TrendBuffering : CimTrendPtBuffer
    object contains the trend point buffering information for a CIMPLICITY point
    Duration : integer
    is a long integer containing maximum age in seconds of a sample to keep
    MaxBuffered : integer
    is a long integer containing the maximum number of samples to keep
    TriggerCheckPointID : string
    is an string containing the name of the availability trigger for the point. When the availability trigger is non-zero and available the point will be available, otherwise the point is unavailable. Defaults to the empty string when creating a new point
    TriggerPointID : string
    is a string indicating the name of the trigger point. Trigger points are valid only for device points and some derived points. When configured for a device point, the trigger point must be on the same device as the point you are defining. Defaults to the empty string when creating a new point
    Type : CimPointOriginEnum
    defines the orgin types for a point
    changeapproval : CimChangeapprovalEnum
    defines different change approval data setting. The numeric value of these enumerations can be used in an expression of a class data item for the $APPROVAL_TYPE field
    OpcUaDeviceContexts : Array[CimOpcUaDeviceContext]
    DeviceId : string
    The Id of the OPC UA device.
    NamespaceUris : Array[string]
    An array of URIs referenced by NodeIds or QualifiedNames in the request. NamespaceIndex 0 shall not be in this list. The first entry in this list is NamespaceIndex 1.
    ServerUris : Array[string]
    A list of URIs referenced by ExpandedNodeIds in the request. ServerIndex 0 shall not be in this list. The first entry in this list is ServerIndex 1.
    DynCreate : boolean
    200 Response

    The response body is of type PointsPostResponse.

    The collection of respondes from the point create/update operation

    Overview

    PointsPostResponse
    The results of the point create/update/delete operations.
    NumSuccesses : number
    The number of points that were successfully written.
    NumFailures : number
    The number of points that failed to be written.
    WarningsMask : integer
    a bitmask of warning conditions (e.g., WarningLicensePointCount)
    PointResults : Array[ItemResult]
    The results for each point in the request array.
    Success : boolean
    high level result (success true, failure false)
    StatusDetails : integer
    a value giving more details about the status (e.g., SuccessNew, SuccessModified, FailureDupInRequest, FailureDupInObject, and then a bunch of FailureXyzzy, ...)
    WarningsMask : integer
    a bitmask of warning conditions (e.g., IE_SNF_NO_GLB_TRIG_MSG)
    Message : string
    (localized?) message about the result, probably empty for successes
    Fault Responses
    FaultDescription
    This fault returns a response body of type ProblemDetails.
    Error if objects not found
    This fault returns a response body of type ProblemDetails.
    General error